AGC Master and AGC Slave Extinguishing Apparatuses

Installation of Extinguishing Apparatuses

You may submit your request for proposal here.

AGC Master and Slave Extinguishing Apparatuses are designed to be installed on the top shelf of the cabinet (fig.4). The devices have to be installed horizontally. Free space under the panel must be exact of 2U 1U=1¾”=44.45mm). When the AGC Master Extinguishing Apparatus is situated on the left side, AGC Slave Extinguishing Panels must be installed on the right side


View of Extinguishing Apparatuses AGC Master and AGC Slave installed in the cabinets

Fig. 1. View of Extinguishing Apparatuses AGC Master and AGC Slave installed in the cabinets.

In this case three or four cabinets create one cubic space where AGC Master Extinguishing Apparatus is applicable for three cabinets and AGC Slave Extinguishing Apparatus for four cabinets – the arrangement of the devices in the cabinet fig. 2 and fig. 3.


AGC Master and AGC Slave Extinguishing Apparatuses fitted into four joined cabinets

Fig. 2. AGC Master and AGC Slave Extinguishing Apparatuses fitted into four joined cabinets which create one cubic space.

Dwa Aparaty Gaśnicze AGC Master z dwoma Aparatami Gaśniczymi Slave

Fig. 3. AGC Master and AGC Slave Extinguishing Apparatuses fitted into four joined cabinets which create one cubic space.

The connection between the devices is arranged by a set of patch cords installed in Slave device.


NOTICE! Requirements for the secured cabinets
  • Extinguishing Apparatus AGC Master and AGC Slave can only be applied in server cabinets (or other cabinets compatible with this type of device) whose air-tightness enables a required concentration of HFC 236fa (FE-36) extinguishing agent to maintain after the release of gas. The cabinets must be air-tight from the sides (no perforation, gaps, holes etc.). Cabinets may have ventilators but they need to be extra-air-tightened with nonwoven fabric (offered by manufacturers producing devices of this kind). It is also advised to fit a cabinet with a actuator operated damper in order to increase air-tightness of the cabinet during fire extinguishing. The bottom of the cabinet should be wadded or its air-tightness should be increased by the application of an actuator operated damper.
  • It is crucial to remember that cabinet’s door and other parts of the case (side doors and other moving objects) must be hermetically closed. Only air-tight zone guarantees the required concentration of HFC 236fa (FE-36) gas in the case of the fire.